Siempre es más fácil conocer las normas ENEL-CODENSA
Rolex Rolex gold watch, compared with ordinary materials, gold watches are often expensive, but the replica rolex gold watch has the role of swiss replica watches hedging, so that it often becomes the first choice for collectors. The gold watch has value in the world, largely because the omega replica watch brand launched a commemorative limited edition watch or a replica hublot complex movement process or artistic attainments deep watches, mostly preferred gold precious metals such material. These watches tend to have a strong hedging function, therefore, Rolex Rolex gold watch reputation.
Norma técnica

Generalidades 7.4.2 Formas para medir la energía según la carga contratada

Datos adicionales
Número de la norma
Generalidades 7.4.2
Fecha de vigencia
20/01/2017
Herramientas adicionales

7.4.2. FORMAS PARA MEDIR LA ENERGÍA DE ACUERDO CON LA CARGA

Para servicios cuya carga requerida sea inferior a cincuenta y cinco (55) kW, la medida se realizará en baja tensión (nivel 1) con medidores de energía electrónicos con clase de exactitud igual o mejor a 1, en conexión directa o semidirecta por medio de transformadores de corriente con clase de exactitud igual o mejor a 0.5S. Estos equipos pueden ser multirango en tensión hasta 480 V.

Para cargas iguales o superiores a cincuenta y cinco (55) kW, e inferiores a trescientos (300) kW, la medida se realizará en baja tensión (nivel 1) con medidores de energía electrónicos y transformadores de corriente con clase de exactitud igual o mejor a 0.5S. Como mínimo deben registrar la siguiente información:

También debe poseer puerto de comunicaciones RS232, RS485 y/o Ethernet

Para cargas superiores a 300kW, la medida se realizará en media tensión (nivel 2 o 3) con medidores de energía electrónicos y transformadores de corriente con clase de exactitud igual o mejor a 0.2S, y transformadores de tensión con clase de exactitud igual o mejor a 0.2. Como mínimo deben registrar la siguiente información:
También debe poseer puerto de comunicaciones RS232, RS485 y/o Ethernet

La conexión indirecta (con CT´s y PT’s) se debe realizar solo en tres (3) elementos.

Se podrá realizar medición en nivel de tensión 2 o 3 para cargas menores a 300kW, con aprobación previa de CODENSA S.A. ESP para cada caso en particular.

7.4.2.1. LÍMITES DE CARGA PARA MEDICIÓN DIRECTA

En la selección de los conductores de la acometida, debe tenerse en cuenta que cumpla con los requerimientos de caída máxima de tensión de acuerdo con la norma AE 200. En las siguientes tablas se señalan los calibres mínimos a utilizar.
No.Sistema de AlimentaciónTensión nominal y corriente básica del medidorCorriente máxima del medidor (A)Calibre mínimo de la acometida conductor de cobre AWG (mm²)Capacidad del Conductor (A)
Monopolar (subterráneo)Antifraude o trenzado (Aéreo)
THW (75°C)THWN-2 (90°C)
1Monofásico bifilar 120 V1 x 120 V - 10 A1002 x 4 (2 x 16)769571
1 x 120 V - 15 A1002 x 6 (2 x 10)657552
2 x 8 (2 x 6)505538
2Bifásico trifilar 120/208 V2 x 120/208 V - 10 A 1002 x 4 + 1 x 6 (3 x 16)859571
2 x 120/208V - 15A1002 x 6 + 1 x 8 (3 x 10)657552
2 x 8 + 1 x 10 (3 x 6)505538
3Trifásico tetrafilar 120/208 V3 x 120/208V - 10A 1003 x 4 + 1 x 6 (4 x 16)859591
3 x 120/208 V - 15 A1203 x 6 + 1 x 8 (4 x 10)657569
3 x 8 + 1 x 10 (4 x 6)505553
4Trifásico tetrafilar 120/208 V3 x 120/208 V - 50 A1503 x 1/0 + 1 x 2 (3 x 70+1 x 35) 150170---
3 x 2 + 1 x 4 (3 x 35 + 1 x 15)130
5Trifásico tetrafilar 277/480 V3 x 277/480 V - 10 A 1003 x 4 + 1 x 6 (4 x 16)859591
3 x 277/480 V - 15 A120
6Trifásico tetrafilar 220/380V3 x 220/380 V – 10 A1003 x 4 + 1 x 6 (4 x 16)859591
3 x 220/380 V – 15 A120

7.4.2.2. LÍMITES DE CARGA PARA MEDICIÓN INDIRECTA EN B.T.

7.4.2.2.1. CARGAS ALIMENTADAS CON TRANSFORMADOR DE DISTRIBUCIÓN DE USO DEDICADO Y MEDIDA EN B.T.: 120/208 V
No.Capacidad del transformador (kVA)Corriente nominal B.T. (A)Transformadores de CorrienteTensiones y corrientes nominales del medidorCalibre mínimo de acometida Cobre
THW (75°C)THWN-2 (90°C)
1752083 x 200:53 x 120/208 V 5 A3 x 4/0 + 1 x 2/03 x 4/0 + 1 x 2/0
2112,53123 x 300:53 x 120/208 V 5 A3 x 500 + 1 x 2503 x 350 + 1 x 4/0
31504163 x 400:53 x 120/208 V 5 A6 x 4/0 + 3 x 4/03 x 500 + 1 x 250
42256243 x 600:53 x 120/208 V 5 A6 x 350 + 3 x 2506 x 350 + 3 x 250
53008323 x 800:53 x 120/208 V 5 A
640011113 x 1000:53 x 120/208 V 5 A
750013883 x 1200:53 x 120/208 V 5 A


7.4.2.2.2. CARGAS ALIMENTADAS CON TRANSFORMADORES DE DISTRIBUCIÓN DE USO DEDICADO Y MEDIDA EN BAJA TENSIÓN: 277/480 V
No.Capacidad del transformador (kVA)Corriente nominal B.T.(A)Transformadores de CorrienteTensiones y corrientes nominales del medidorCalibre mínimo de acometida Cobre
THW (75°C)THWN-2 (90°C)
175903 x 100:53 x 277/480 V 5 A3 x 2 + 1 x 43 x 4 + 1 x 6
2112,51353 x 200:53 x 277/480 V 5 A3 x 1/0 + 1 x 23 x 1/0 + 1 x 2
31501803 x 200:53 x 277/480 V 5 A3 x 4/0 + 1 x 2/03 x 2/0 + 1 x 2
42252713 x 300:53 x 277/480 V 5 A3 x 350 + 1 x 4/03 x 250 + 1 x 4/0
53003603 x 400:53 x 277/480 V 5 A3 x 500 + 1 x 3003 x 500 + 1 x 300
64004813 x 500:53 x 277/480 V 5 A6 x 250 + 2 x 2/06 x 4/0 + 2 x 2/0
75006013 x 600:53 x 277/480 V 5 A6 x 350 + 2 x 4/06 x 350 + 2 x 4/0

7.4.2.3. LÍMITES DE CARGA PARA MEDICIÓN INDIRECTA

7.4.2.3.1. CARGAS ALIMENTADAS CON REDES DE M.T. (11,4 kV)
No.Capacidad de transformación (kVA)Corriente primaria nominal (A)Transformador de CorrienteTransformador de potencialMedidor
Tres elementos
1112,55,75:5
3 x 58/100…277/480 V 5 A Multirango en tensión
21507,67,5:5
322511,410:5
430015,215:5
540020,320:5
650025,330:5
760031,930:5
880040,540:5
910005050:5
1015007575:5


7.4.2.3.2. CARGAS ALIMENTADAS CON REDES DE M.T. (13,2 kV)
No.Capacidad de transformación (kVA)Corriente primaria nominal (A)Transformador de CorrienteTransformador de potencialMedidor
140017,520:5
3 x 58/100…277/480 V 5 A Multirango en tensión
250021,8720:5
360026,230:5
48003540:5


7.4.2.3.3. CARGAS ALIMENTADAS CON LINEAS PRIMARIAS DE 34,5 kV
No.Capacidad de transformación kVACorriente primaria nominal (A)Transformador de CorrienteMedida en tres elementos
Transformador de potencialMedidor
15008.310:5
3 x 115/200 V
5A
280013.315:5
3 x 115/200 V
5A
3100016.620:5
3 x 115/200 V
5A
4140023,430:5
3 x 115/200 V
5A
5150025,130:5
3 x 115/200 V
5A
6200033,530:5
3 x 115/200 V
5A
730005060:5
3 x 115/200 V
5A
8400066,960:5
3 x 115/200 V
5A
9500087,7100:5
3 x 115/200 V
5A


Para la definición de I nominal y la I máxima, en los medidores de energía, se deben tener en cuenta que la corriente secundaria de los CT’s que utiliza CODENSA para grandes consumidores, es 5 A, y como la máxima corriente permitida por los CT’s es del 120% equivalente a una Imáxima del secundario de grandes consumidores, por consiguiente los valores fundamentales para la selección de un medidor en lo referente a la corriente son:

a) I máxima: Corriente máxima. El mayor valor de corriente en la cual el medidor debe cumplir con su requisito de precisión. Para CODENSA, I máxima = 6 A. o 10 A
b) I nominal: Valor de la corriente con el cual se fija el desempeño correspondiente de un medidor conectado a transformador. Para CODENSA, I nominal = 5A

Para casos especiales como fronteras comerciales se utilizan:

I máxima: 2A
I nominal: 1A